Three Elements Numerical Differential/ Over Current Protection Relay

Product Profile of Three Elements Numerical Differential/ Over Current Protection Relay
Three Elements Numerical Differential/ Over Current Protection Relay enables Instantaneous Over-Current Protection with adjustable Timer and has the facility of Internal calculation of zero seq. EF current. The Differential/ Over Current Protection Relay also protects against negative sequence over current. Ashida Eletronics Pvt. Ltd., an ISO 9001:2008 certified company manufactures Three Elements Numerical Differential/ Over Current Protection Relay.

Ashida Eletronics Pvt. Ltd. offers a wide range of electrical power protection relays, auxiliary protection relay and SCADA systems. The Three Elements Numerical Differential/ Over Current Protection Relay allows Programmable starting current and dual bias setting.

Salient features of the Three Elements Numerical Differential/ Over Current Protection Relay:

  • Transformer Differential + Over Current + Restricted Earth Fault.
  • 3 Element [3 Phase + 3Io] Over current IDMT/DMT with instant Trip.
  • Selection of Curve: Five selectable curve- Normal Inverse, Very Inverse, Extremely Inverse, Long Time Inverse and Define Time.
  • Programmable starting current and dual bias setting.
  • Harmonic Restrain for Transformer charging and CT saturation condition.
  • Unrestrained Differential Protection.
  • Programmable Internal ICT [Interposing CT] ratio to match different transformer having different vector groups.
  • In-built CB Trip Circuit Supervision function during pre closing and post closing of CB.
  • Breaker Failure Detection.
  • Disturbance Recorder. Up to 3 sec of actual waveform of current along with logical and physical status are captured and saved in the built-in memory, with date time stamping for analyzing fault condition & fault location.
  • Fully communicable with IEC 60870-5-103.
  • Continuously monitors the module`s internal hardware and alarm is generated in case of failure of any critical components
  • Large 20X4 LCD display for Parameter and setting display. On site CT Secondary selection 1A or 5A.
  • Very low burden on CT [less than 0.2VA]
  • Operation based on fundamental frequency value.
  • Latching of fault current value.
  • 8 Digital Output contacts for local Alarm as well as Tele-signalling.